ABB FCAN 01 User Manual

Options for ABB drives, inverters and converters  
User’s manual  
FCAN-01 CANopen adapter module  
User’s manual  
FCAN-01 CANopen adapter module  
Table of contents  
1. Safety  
4. Mechanical installation  
5. Electrical installation  
6. Start-up  
3AFE68615500 Rev D  
EN  
EFFECTIVE: 2012-01-25  
© 2012 ABB Oy  
All Rights Reserved.  
Table of contents  
5
Table of contents  
1. Safety  
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
Use of warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
Safety in installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
2. About the manual  
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
Target audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
Purpose of the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
Related manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
Before you start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
Terms and abbreviations used in this manual . . . . . . . . . . . . . . 19  
Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
CANopen abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
3. Overview of the CANopen protocol and the FCAN-01  
adapter module  
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
CANopen protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
Topology of the CANopen link . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
FCAN-01 CANopen adapter module . . . . . . . . . . . . . . . . . . . . . 25  
Layout of the adapter module . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
4. Mechanical installation  
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
Delivery check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
Mounting the adapter module . . . . . . . . . . . . . . . . . . . . . . . . . . 28  
5. Electrical installation  
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
 
6 Table of contents  
Connecting the module to the CANopen network . . . . . . . . . . . 30  
Bus termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
AC and DC parameters for the CANopen network . . . . . . . . . . . 32  
Bus cable and termination resistors . . . . . . . . . . . . . . . . . . . 32  
6. Start-up  
Drive configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
CANopen connection configuration . . . . . . . . . . . . . . . . . . . 36  
Data transfer rates supported. . . . . . . . . . . . . . . . . . . . . 36  
FCAN-01 configuration parameters – group A (group 1) 37  
FCAN-01 configuration parameters – group B (group 2) 51  
FCAN-01 configuration parameters – group C (group 3) 54  
allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57  
Control locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58  
Starting up ACS355 drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58  
Parameter setting examples – ACS355 . . . . . . . . . . . . . . . . 59  
CiA 402 vl velocity mode with default PDO mapping . . . 59  
Speed and torque control using ABB Drives  
communication profile with parameter-configured PDO  
mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61  
Starting up ACSM1 drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64  
Parameter setting examples – ACSM1 . . . . . . . . . . . . . . . . 66  
Using position control with the CiA 402 Profile Position  
mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66  
Starting up ACS850 drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69  
Parameter setting examples – ACS850 . . . . . . . . . . . . . . . . 70  
CiA 402 Velocity mode with default PDO mapping . . . . 70  
ABB Drives communication profile with parameter-  
configured PDO mapping . . . . . . . . . . . . . . . . . . . . . . . . 72  
Starting up ACS880 drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75  
Parameter setting examples – ACS880 . . . . . . . . . . . . . . . . 76  
CiA 402 Velocity mode with default PDO mapping . . . . 76  
Configuring the master station . . . . . . . . . . . . . . . . . . . . . . . . . . 78  
Table of contents  
7
EDS files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78  
Configuring an ABB AC500 PLC . . . . . . . . . . . . . . . . . . . . . 79  
7. Communication profiles  
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87  
Communication profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87  
CANopen device profile CiA 402 . . . . . . . . . . . . . . . . . . . . . . . . 89  
Device Control state machine . . . . . . . . . . . . . . . . . . . . . . . 89  
Modes of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90  
Homing mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90  
Profile position mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91  
Position demand value. . . . . . . . . . . . . . . . . . . . . . . . . . 91  
Position actual value . . . . . . . . . . . . . . . . . . . . . . . . . . . 91  
Interpolated position mode . . . . . . . . . . . . . . . . . . . . . . . . . 91  
Profile velocity mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91  
Target velocity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92  
Velocity actual value . . . . . . . . . . . . . . . . . . . . . . . . . . . 92  
Profile torque mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92  
Target torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92  
Torque actual value . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92  
Velocity mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93  
Target velocity of CiA 402 Velocity mode . . . . . . . . . . . 93  
Control effort of CiA 402 Velocity mode. . . . . . . . . . . . . 93  
Control word and Status word of the CiA 402 profile . . . . . . 93  
State machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99  
ABB Drives communication profile . . . . . . . . . . . . . . . . . . . . . . 100  
Control word and Status word . . . . . . . . . . . . . . . . . . . . . . 100  
Control word contents . . . . . . . . . . . . . . . . . . . . . . . . . 100  
Status word contents . . . . . . . . . . . . . . . . . . . . . . . . . . 103  
State machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105  
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106  
Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106  
Actual values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107  
Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107  
8 Table of contents  
8. Communication protocol  
CAN data frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109  
FCAN-01 boot-up sequence and  
Rx PDO1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114  
Tx PDO1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115  
Rx PDO6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116  
Tx PDO6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117  
Rx PDO21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118  
Tx PDO21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119  
Mapping format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120  
PDO configuration via the CAN bus . . . . . . . . . . . . . . . . . . . . . 121  
Service Data Objects (SDO) . . . . . . . . . . . . . . . . . . . . . . . . . . 124  
SDO Download . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124  
SDO Upload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125  
Read Service (SDO Upload) . . . . . . . . . . . . . . . . . . . . . . . . . . 126  
Initiate SDO Upload Protocol . . . . . . . . . . . . . . . . . . . . . . . 126  
Write Service (SDO Download) . . . . . . . . . . . . . . . . . . . . . . . . 127  
Initiate SDO Download Protocol . . . . . . . . . . . . . . . . . . . . 127  
Abort SDO Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128  
Abort SDO Transfer Protocol . . . . . . . . . . . . . . . . . . . . . . . 128  
Abort code description . . . . . . . . . . . . . . . . . . . . . . . . . 129  
CANopen Object Dictionary . . . . . . . . . . . . . . . . . . . . . . . . . . . 131  
Object Dictionary Structure . . . . . . . . . . . . . . . . . . . . . . . . 131  
Communication profile area (1000...1FFF) . . . . . . . . . . . . 132  
Manufacturer-specific profile area (2000...5FFF) . . . . . . . . 142  
Manufacturer-specific profile objects . . . . . . . . . . . . . . 142  
Drive actual signals and parameters . . . . . . . . . . . . . . 143  
Standardized device profile area (6000...9FFF) . . . . . . . . 145  
9. Diagnostics  
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151  
LED indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151  
Table of contents  
9
10. Technical data  
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153  
FCAN-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154  
CANopen link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155  
11. Appendix A – Dictionary structure and entries  
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157  
Description of transmission type . . . . . . . . . . . . . . . . . . . . . . . 158  
Description of PDO COB-ID entry . . . . . . . . . . . . . . . . . . . . . . 158  
PDO mapping entry structure – example . . . . . . . . . . . . . . . . . 159  
12. Appendix B – CANopen error codes  
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161  
Error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161  
Further information  
Product and service inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . 171  
Product training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171  
Providing feedback on ABB Drives manuals . . . . . . . . . . . . . . 171  
Document library on the Internet . . . . . . . . . . . . . . . . . . . . . . . 171  
10 Table of contents  
Safety 11  
1
Safety  
What this chapter contains  
The chapter presents the warning symbols used in this manual and  
the safety instructions which you must follow when installing an  
optional module into a drive, converter or inverter. If ignored,  
physical injury or death may follow, or damage may occur to the  
equipment. Read this chapter before you start the installation.  
     
12 Safety  
Use of warnings  
Warnings caution you about conditions which can result in serious  
injury or death and/or damage to the equipment and advise on how  
to avoid the danger. The following warning symbols are used in  
this manual:  
Electricity warning warns of hazards from electricity  
which can cause physical injury and/or damage to the  
equipment.  
General warning warns about conditions, other than  
those caused by electricity, which can result in physical  
injury and/or damage to the equipment.  
 
Safety 13  
Safety in installation  
These warnings are intended for all who install an optional module  
into a drive, converter or inverter.  
WARNING! Ignoring the following instructions can cause  
physical injury or death, or damage to the equipment.  
Only qualified electricians are allowed to install and maintain  
the drive, converter or inverter!  
Disconnect the drive, converter or inverter into which the  
optional module will be installed from all possible power  
sources. After disconnecting, always wait for 5 minutes to let  
the intermediate circuit capacitors discharge before you  
proceed.  
Always ensure by measuring with a multimeter (impedance at  
least 1 Mohm) that:  
there is no voltage between the input power terminals of  
the drive, converter or inverter and the ground  
there is no voltage between the output power terminals of  
the drive, converter or inverter and the ground.  
Do not work on the control cables when power is applied to the  
external control circuits of the drive, converter or inverter.  
Externally supplied control circuits may carry dangerous  
voltage.  
 
14 Safety  
About the manual 15  
2
About the manual  
What this chapter contains  
This chapter introduces this manual.  
Applicability  
This manual applies to the FCAN-01 CANopen adapter module  
(+K457), SW version 1.046 or later.  
Compatibility  
The FCAN-01 CANopen adapter module is compatible with the  
following drives:  
ACS355  
ACSM1  
ACS850  
ACS880.  
Target audience  
The reader is expected to have basic knowledge of fieldbus  
interface, electrical fundamentals, electrical wiring practices and  
how to operate the drive.  
         
16 About the manual  
Purpose of the manual  
The manual provides information on installing, commissioning and  
using an FCAN-01 CANopen adapter module.  
Related manuals  
The related manuals are listed below.  
Code (English)  
Drive user’s manuals  
ACS355 drives (0.37…22 kW,  
0.5…30 hp) user’s manual  
Drive hardware manuals and  
guides  
ACSM1-204 regen supply modules 3AUA0000053713  
(5.3 to 61 kW) hardware manual  
ACSM1-04 drive modules (0.75 to 3AFE68797543  
45 kW) hardware manual  
ACSM1-04 drive modules (55 to  
110 kW) hardware manual  
ACSM1-04Lx liquid-cooled drive  
modules (55 to 160 kW) hardware  
manual  
ACS850-04 (0.37…45 kW)  
hardware manual  
ACS850-04 (55…160 kW, 75…200 3AUA0000045487  
hp) hardware manual  
ACS850-04 (200…500 kW,  
250…600 hp) hardware manual  
ACS880-01 (0.55 to 250 kW, 0.75 3AUA0000078093  
to 350 hp) hardware manual  
     
About the manual 17  
Code (English)  
Drive firmware manuals and  
guides  
ACSM1 motion control program  
firmware manual  
ACSM1 speed and torque control 3AFE68848261  
program firmware manual  
ACSM1 regen supply control  
program firmware manual  
ACS850 standard control program 3AUA0000045497  
firmware manual  
ACS880 primary control program  
firmware manual  
Option manuals and guides  
FCAN-01 CANopen adapter  
module user’s manual  
You can find manuals and other product documents in PDF format  
on the Internet. See section Document library on the Internet on  
the inside of the back cover. For manuals not available in the  
Document library, contact your local ABB representative.  
Before you start  
It is assumed that the drive is installed and ready to operate before  
you start the installation of the adapter module.  
In addition to conventional installation tools, have the drive  
manuals available during the installation as they contain important  
information not included in this manual. The drive manuals are  
referred to at various points of this manual.  
 
18 About the manual  
Contents  
The manual consists of the following chapters:  
Safety presents the safety instructions which you must follow  
when installing a fieldbus adapter module.  
About the manual introduces this manual.  
Overview of the CANopen protocol and the FCAN-01 adapter  
module contains a short description of the CANopen protocol  
and the adapter module.  
Mechanical installation contains a delivery checklist and  
instructions on mounting the adapter module.  
Electrical installation contains wiring and bus termination  
instructions.  
Start-up presents the steps to take during the start-up of the  
drive with the adapter module and gives examples of  
configuring the master system.  
Communication profiles describes the communication profiles  
used in communication between the CANopen network, the  
adapter module and the drive.  
Communication protocol describes the communication on a  
CANopen network.  
Diagnostics explains how to trace faults with the status LEDs  
on the adapter module.  
Technical data contains the technical data of the adapter  
module and the CANopen link.  
Appendix A – Dictionary structure and entries contains  
information about PDO transmission and mapping.  
Appendix B – CANopen error codes contains reference tables  
for decoding CANopen error messages.  
 
About the manual 19  
Terms and abbreviations used in this manual  
Terms  
Term  
Explanation  
Communication module Communication module is a name for a device  
(eg, a fieldbus adapter) through which the drive  
is connected to an external communication  
network (eg, a fieldbus). The communication  
with the module is activated with a drive  
parameter.  
Command word  
Control word  
See Control word.  
16-bit or 32-bit word from master to slave with  
bit-coded control signals (sometimes called the  
Command word)  
FCAN-01 CANopen  
adapter module  
One of the optional fieldbus adapter modules  
available for ABB drives. FCAN-01 is a device  
through which an ABB drive is connected to a  
CANopen network.  
Object dictionary  
Parameter  
Local storage of all Communication Objects  
(COB) recognized by a device  
Operating instruction for the drive. Parameters  
can be read and programmed with the drive  
control panel, drive PC tools or through the  
adapter module.  
Profile  
Adaptation of the protocol for certain application  
field, for example, drives. In this manual, drive-  
internal profiles (eg, DCU or FBA) are called  
native profiles.  
Status word  
16-bit or 32-bit word from slave to master with  
bit-coded status messages  
   
20 About the manual  
CANopen abbreviations  
Abbreviation  
CAN  
Explanation  
Controller Area Network  
CiA  
CAN in Automation, International User’s and  
Manufacturer’s Group  
CMS  
CAN Message Specification; one of the service  
elements of the CAN Application Layer in the  
CAN Reference Model  
COB  
DBT  
Grouping of pre-defined data objects accessible  
via the network.  
Distributor; one of the service elements of the  
CAN Application Layer in the CAN Reference  
Model. It is the responsibility of the Distributor to  
distribute COB IDs to the COBs that are used  
by a CMS.  
EDS  
LMT  
Electronic Data Sheet; a node-specific ASCII-  
format file required when configuring the CAN  
network. The EDS file contains general  
objects (parameters). EDS files for ABB Drives  
are available at the Document library  
(www.abb.com/drives).  
Layer Management; one of the service  
elements of the CAN Application Layer in the  
CAN Reference Model. It serves to configure  
parameters for each layer in the CAN  
Reference Model.  
LSB  
MSB  
NMT  
Least significant bit/byte  
Most significant bit/byte  
Network Management; one of the service  
elements of the CAN Application Layer in the  
CAN Reference Model. It performs initialization,  
configuration and error handling on a CAN  
network.  
OSI  
Open Systems Interconnection  
PDO  
Process Data Object; a type of COB. Used for  
transmitting time critical data, such as control  
commands, references and actual values.  
 
About the manual 21  
Abbreviation  
Explanation  
RO  
Denotes read-only access.  
Denotes read/write access.  
RW  
SDO  
Service Data Object; a type of COB. Used for  
transmitting non-time-critical data, such as  
parameters.  
22 About the manual  
Overview of the CANopen protocol and the FCAN-01 adapter module 23  
3
Overview of the CANopen  
protocol and the FCAN-01  
adapter module  
What this chapter contains  
This chapter contains a short description of the CANopen protocol  
and the FCAN-01 CANopen adapter module.  
CANopen protocol  
CANopen is a higher layer protocol based on the CAN (Control  
Area Network) serial bus system and the CAL (CAN Application  
Layer). CANopen assumes that the hardware of the connected  
device has a CAN transceiver and a CAN controller as specified in  
ISO 11898.  
The CANopen Communication Profile, CiA 301, includes both  
cyclic and event driven communication, which makes it possible to  
reduce the bus load to minimum while still maintaining extremely  
short reaction times. High communication performance can be  
achieved at relatively low baud rates, thus reducing EMC problems  
and cable costs.  
CANopen device profiles define both direct access to drive  
parameter and time critical process data communication. The  
adapter module fulfills CiA (CAN in Automation) specification CiA  
402 (CANopen device profile for drives and motion control).  
       
24 Overview of the CANopen protocol and the FCAN-01 adapter module  
The physical medium of CANopen is a differentially driven two wire  
bus line with common return according to ISO 11898. The  
maximum length of the bus is limited by the communication speed.  
The maximum theoretical number of nodes is 127. However, in  
practice, the maximum number depends on the capabilities of the  
used CAN transceivers.  
Further information is available from the CAN in Automation  
International Users and Manufacturers Group (www.can-cia.org).  
Topology of the CANopen link  
The following figure describes the topology of the CANopen link.  
ABB drive  
Other slave  
device  
ABB drive  
CANopen  
master  
T
Other slave  
device  
ABB drive  
Other slave  
device  
ABB drive  
T
T = Termination  
 
Overview of the CANopen protocol and the FCAN-01 adapter module 25  
FCAN-01 CANopen adapter module  
The FCAN-01 CANopen adapter module is an optional device for  
ABB drives. It enables the connection of the drive to a CANopen  
network. The drive is considered as a slave (server) on the  
CANopen network.  
Through the adapter module you can:  
give control commands to the drive  
(for example, Start, Stop, Run enable)  
feed a motor speed, torque or position reference to the drive  
give a process actual value or a process reference to the PID  
controller of the drive  
read status information and actual values from the drive  
change drive parameter values  
reset a drive fault.  
The CANopen commands and services supported by the adapter  
module are discussed in chapter Communication protocol. Refer to  
the drive manuals as to which commands are supported by the  
drive.  
The adapter module is mounted into an option slot on the motor  
control board of the drive. See the drive manuals for module  
placement options.  
 
26 Overview of the CANopen protocol and the FCAN-01 adapter module  
Layout of the adapter module  
The following figure describes the layout of the adapter module.  
Diagnostic LEDs  
(see chapter Diagnostics)  
Bus connector X1  
(see chapter Electrical  
installation)  
Mounting screw  
 
Mechanical installation 27  
4
Mechanical installation  
What this chapter contains  
This chapter contains a delivery checklist and instructions on  
mounting the adapter module.  
WARNING! Follow the safety instructions given in this  
manual and the drive documentation.  
Delivery check  
The option package for the adapter module contains:  
CANopen adapter module, type FCAN-01  
this manual.  
       
28 Mechanical installation  
Mounting the adapter module  
The adapter module is inserted into its specific position in the drive.  
The module is held in place with plastic pins and one screw. The  
screw also provides the electrical connection between the module  
and drive frame for cable shield termination.  
When the module is installed, the signal and power connection to  
the drive is made through a 20-pin connector. (All drives do not use  
all the available signals so the connector on the drive may have  
fewer pins.)  
Mounting procedure:  
1. Insert the module carefully into its position on the drive.  
2. Fasten the screw.  
Note: It is essential to install the screw properly to fulfill the EMC  
requirements and to ensure the proper operation of the module.  
For more information on mounting the adapter module, see the  
drive manuals.  
 
Electrical installation 29  
5
Electrical installation  
What this chapter contains  
This chapter contains:  
general cabling instructions  
bus termination instructions  
instructions on connecting the adapter module to the CANopen  
network.  
WARNING! Before installation, switch off the drive power  
supply. Wait five minutes to ensure that the capacitor bank  
of the drive is discharged. Switch off all dangerous  
voltages connected from external control circuits to the inputs and  
outputs of the drive.  
General cabling instructions  
Arrange the bus cables as far away from the motor cables as  
possible.  
Avoid parallel runs.  
Use bushings at cable entries.  
       
30 Electrical installation  
Connecting the module to the CANopen network  
Connect the bus cable to connector X1 on the adapter module.  
The connector pin allocation described below follows the CANopen  
specification CiA 301.  
1
5
SUB-D9  
(male)  
X1  
X1  
6
9
Description  
1
2
3
4
5
6
7
8
9
-
Not in use  
CAN_L  
CAN_L bus line (dominant low)  
CAN ground  
CAN_GND  
-
Not in use  
CAN_SHLD Optional CAN shield  
GND  
Optional ground  
CAN_H  
-
CAN_H bus line (dominant high)  
Not in use  
CAN_V+  
Optional CAN external power supply. Not supported  
by FCAN-01.  
 
Electrical installation 31  
Bus termination  
Bus termination is required to prevent signal reflections from the  
bus cable ends. The adapter module is not equipped with internal  
bus termination. Therefore the first and last nodes of the bus must  
be included with bus termination. Termination is done by  
connecting one resistor between the CAN_H and CAN_L signals.  
The nominal value for the terminating resistor is 120 ohms. The  
resistors can be connected between the CAN_H and CAN_L wires  
or a D-SUB connector with a built-on termination can be used.  
In the following diagram, the built-on terminations of the D-SUB  
connectors at the first and last nodes are switched on.  
CANopen  
node  
CANopen  
node  
CANopen  
node  
CANopen  
node  
Term.  
ON  
Term.  
OFF  
Term.  
OFF  
Term.  
ON  
In the following diagram, the bus line is terminated with 121 ohm,  
1 % (E96) resistors connected between the CAN_L and CAN_H  
wires at each end.  
CANopen  
node  
CANopen  
node  
CANopen  
node  
CAN_H  
121 ohm  
1%  
Metal Film  
1/4 W  
121 ohm  
1%  
Metal Film  
1/4 W  
CAN_L  
www.can-cia.org.  
 
32 Electrical installation  
AC and DC parameters for the CANopen network  
Bus cable and termination resistors  
The cables, connectors, and termination resistors used in  
CANopen networks must meet the requirements specified in ISO  
11898.  
The table below lists the standard values for DC parameters for  
CANopen networks with less than 64 nodes:  
1)  
Bus length  
[m]  
Bus cable  
Termination  
resistance  
[ohm]  
Baud rate  
[kbit/s]  
Length-  
related  
resistance  
[mohm/m]  
Cross-  
section  
[mm ]  
2
0…40  
70  
0.25…0.34 124  
1000 at 40 m  
> 500 at 100 m  
> 100 at 500 m  
> 50 at 1 km  
40…300  
300…600  
< 60  
< 40  
0.34…0.6  
0.5…0.6  
0.75…0.8  
150…300  
150…300  
150…300  
600…1000 < 26  
1)  
Recommended cable for AC parameters: 120 ohm impedance and 5  
ns/m line delay  
With drop cables the recommended cable cross-section is  
0.25…0.34 mm2.  
In addition to the cable resistance, the real resistance of the  
connectors should be taken into account in voltage drop  
calculation. The transmission resistance of one connector should  
be 2.5...10 mohm.  
The following table lists the maximum bus cable length for different  
node numbers (n), when  
minimum dominant value Vdiff.out.min = 1.5 V  
minimum differential input resistance Rdiff.min = 20 kohm  
requested differential input voltage Vth.max = 1.0 V  
minimum termination resistance RT.min = 118 ohm.  
   
Electrical installation 33  
1)  
2)  
Wire  
Maximum length [m]  
Maximum length [m]  
cross-  
section  
[mm ]  
n = 32  
n = 64  
n = 100 n = 32  
n = 64  
n = 100  
2
0.25  
200  
360  
550  
170  
150  
230  
420  
640  
200  
360  
550  
170  
320  
480  
0.5  
310  
470  
270  
410  
0.75  
1)  
Safety margin of 0.2  
Safety margin of 0.1  
2)  
34 Electrical installation  
Start-up 35  
6
Start-up  
What this chapter contains  
This chapter contains:  
information on configuring the drive for operation with the  
adapter module  
drive-specific instructions on starting up the drive with the  
adapter module  
examples of configuring the master station for communication  
with the adapter module.  
WARNING! Follow the safety instructions given in this  
manual and the drive documentation.  
Drive configuration  
The following information applies to all drive types compatible with  
the adapter module, unless otherwise stated.  
         
36 Start-up  
CANopen connection configuration  
After the adapter module has been mechanically and electrically  
installed according to the instructions in chapters Mechanical  
installation and Electrical installation, the drive must be prepared  
for communication with the module.  
The detailed procedure of activating the module for CANopen  
communication with the drive depends on the drive type. Normally,  
a parameter must be adjusted to activate the communication. See  
the drive-specific start-up sections on pages 58, 64, 69 and 75.  
Once communication between the drive and the adapter module  
has been established, several configuration parameters are copied  
to the drive. These parameters are shown in the tables below and  
must be checked first and adjusted where necessary.  
Note: Not all drives display descriptive names for the configuration  
parameters. To help you identify the parameters in different drives,  
the names displayed by each drive are given in grey boxes in the  
tables.  
An example on how to configure PDOs via the CAN bus is given in  
section PDO configuration via the CAN bus.  
Note: The new settings take effect only when the adapter module  
is powered up the next time or when the fieldbus adapter refresh  
parameter is activated.  
Data transfer rates supported  
The FCAN-01 CANopen adapter module supports the following  
CANopen communication speeds: 50 kbit/s, 100 kbit/s, 125 kbit/s,  
250 kbit/s, 500 kbit/s, 1 Mbit/s.  
Note: 100 kbit/s is not recommended for a new installation.  
   
Start-up 37  
FCAN-01 configuration parameters – group A (group 1)  
Note: The actual parameter group number depends on the drive  
type. Group A (group 1) corresponds to:  
parameter group 51 in ACS355, ACSM1 and ACS850  
parameter group 51 in ACS880 if the adapter is installed as  
fieldbus adapter A or group 54 if the adapter is installed as  
fieldbus adapter B.  
No. Name/Value  
Description  
Default  
setting  
01  
FBA TYPE  
Read-only. Shows the fieldbus adapter type as 1 =  
detected by the drive. Value cannot be adjusted CAN-  
by the user.  
open  
If the value is 0 = None, the communication  
between the drive and the module has not been  
established.  
02  
NODE ID  
Selects the node address of the module.  
Each device on the CANopen network must  
have a unique node identifier. Used to define a  
node identifier for the drive it is connected to.  
3
ACS355:  
FB PAR 2  
ACSM1:  
FBA PAR2  
ACS850:  
FBA par2  
ACS880:  
Node ID  
1…127  
Node address  
   
38 Start-up  
No. Name/Value  
Description  
Default  
setting  
03  
BIT RATE  
Sets the bit rate for the CANopen interface.  
This is user selectable, but must be the same  
on every node on the CANopen network.  
Note: 100 kbit/s is not recommended for a new  
installation.  
3 = 125  
kbit/s  
ACS355:  
FB PAR 3  
ACSM1:  
FBA PAR3  
ACS850:  
FBA par3  
ACS880:  
Bit rate  
0 = 1 Mbit/s  
1 = 500 kbit/s  
2 = 250 kbit/s  
3 = 125 kbit/s  
4 = 100 kbit/s  
5 = 50 kbit/s  
CONF LOC  
1 Mbit/s  
500 kbit/s  
250 kbit/s  
125 kbit/s  
100 kbit/s  
50 kbit/s  
04  
Selects the source of the PDO configuration.  
Note: The first mapping entries of the Tx/Rx  
PDO1 and Tx/Rx PDO6 are fixed in the  
ACS355 drive.  
Note: Make sure that the PLC does not  
overwrite the selected configuration during the  
initialization phase when the configuration is  
taken from the FCAN-01 configuration  
parameter groups.  
0
ACS355:  
FB PAR 4  
ACSM1:  
FBA PAR4  
ACS850:  
FBA par4  
ACS880:  
Conf location  
0 = Network  
PDO configuration via CAN bus: CANopen  
objects 1400h, 1600h, 1405h, 1605h, 1414h,  
1614h, 1800h, 1A00h, 1805h, 1A05h, 1814h  
and 1A14h only.  
1 = Parameters  
PDO configuration with drive parameters:  
adapter module configuration parameter group  
A (group 1), group B (group 2) and group C  
(group 3) (initial values).  
Start-up 39  
No. Name/Value  
Description  
Default  
setting  
05  
PROFILE  
Selects the used communication profile used by 1 = ABB  
the adapter module:  
For more information on the communication  
profiles, see chapter Communication profiles.  
Drives  
ACS355:  
FB PAR 5  
ACSM1:  
FBA PAR5  
ACS850:  
FBA par5  
ACS880:  
Profile  
0 = CiA 402  
CANopen device profile CiA 402 selected  
ABB Drives profile selected  
1 = ABB Drives  
2 = Transp. 16  
3 = Transp. 32  
T16 SCALE  
Transparent 16 profile selected  
Transparent 32 profile selected  
06  
Defines the reference multiplier/actual value  
divisor for the adapter module. The parameter  
is effective only when the Transparent 16 profile  
is selected AND the drive is using the native  
communication profile (for example, DCU or  
FBA) and a 16-bit transparent Reference  
1/Actual value 1.  
99  
ACS355:  
FB PAR 6  
ACSM1:  
FBA PAR6  
ACS850:  
With an ACS355 drive, the speed reference  
from the PLC is multiplied by the value of this  
parameter plus one. For example, if the  
parameter has a value of 99 and a reference of  
1000 given by the master, the reference will be  
multiplied by 99 + 1 = 100 and forwarded to the  
drive as 100000. According to the DCU profile,  
this value is interpreted as a reference of 100  
rpm in the drive.  
FBA par6  
ACS880:  
T16 scale  
With ACSM1, ACS850 and ACS880, setting  
this parameter to 65535 provides the  
approximation of 1 1 rpm.  
0…65535  
Reference multiplier/actual value divisor  
40 Start-up  
No. Name/Value  
Description  
Default  
setting  
07  
RPDO1-COB-ID  
Defines the COB-ID for Rx PDO1.  
Note: It is recommended to use the default  
COB-ID.  
1
ACS355:  
FB PAR 7  
ACSM1:  
FBA PAR7  
ACS850:  
FBA par7  
ACS880:  
RPDO1-COB-ID  
0 = Disable  
Rx PDO1 is not valid (disabled). COB-ID is  
80000200h + Node-ID.  
1 = Default  
Rx PDO1 is valid and configured to use the  
default COB-ID (200h + Node-ID).  
385…1407 (dec) = Rx PDO1 is valid and configured to use a  
181h … 57Fh  
custom COB-ID defined with this parameter.  
COB-ID must be within the allowed PDO COB-  
ID range (181h - 57Fh).  
08  
RPDO1-TR TYPE Defines the Rx PDO1 transmission type. See  
255  
chapter Appendix A – Dictionary structure and  
entries.  
ACS355:  
FB PAR 8  
ACSM1:  
FBA PAR8  
ACS850:  
FBA par8  
ACS880:  
RPDO1-TR type  
0…255 (dec)  
Rx PDO1 transmission type. See section  
Description of transmission type on page 158.  
Start-up 41  
No. Name/Value  
09 RPDO1-EV TIME  
Description  
Default  
setting  
Defines the event time (time-out time) for the  
Rx PDO1 in the asynchronous transmission  
0 =  
Disable  
ACS355:  
FB PAR 9  
mode. If the Rx PDO1 communication between  
the adapter module and the bus master fails,  
the adapter module sets the communication  
between the module and the drive to the off-line  
mode.  
ACSM1:  
FBA PAR9  
ACS850:  
Event timer (time-out timer) elapses as a  
multiple of 1 ms of the entry of this parameter.  
Note: The time-out supervision is activated  
upon a successful reception of an Rx PDO1.  
FBA par9  
ACS880:  
RPDO1-EV time  
0 = Disable  
Time-out supervision is disabled.  
Event time in ms  
1…65535 (ms)  
TPDO1-COB-ID  
10  
Defines the COB-ID for Rx PDO6.  
1 =  
Default  
Note: It is recommended to use the default  
COB-ID.  
ACS355:  
FB PAR 10  
ACSM1:  
FBA PAR10  
ACS850:  
FBA par10  
ACS880:  
TPDO1-COB-ID  
0 = Disable  
Tx PDO1 is not valid (disabled). COB-ID is  
80000180h + Node-ID.  
1 = Default  
Tx PDO1 is valid and configured to use the  
default COB-ID (180h + Node-ID).  
385…1407 (dec) = Tx PDO1 is valid and configured to use a  
181h … 57Fh  
custom COB-ID defined with this parameter.  
COB-ID must be within the allowed PDO COB-  
ID range (181h - 57Fh).  
42 Start-up  
No. Name/Value  
Description  
Default  
setting  
11  
TPDO1-TR TYPE Defines the PDO1 transmission type. See  
255  
chapter Appendix A – Dictionary structure and  
entries.  
ACS355:  
FB PAR 11  
ACSM1:  
FBA PAR11  
ACS850:  
FBA par11  
ACS880:  
TPDO1-TR type  
0…255 (dec)  
PDO1 transmission type. See section  
Description of transmission type on page 158.  
12  
TPDO1-EV TIME  
Defines the event time for the Tx PDO1  
asynchronous transmission mode.  
Event timer elapses as a multiple of 1 ms of the  
entry of this parameter.  
0 =  
Disable  
ACS355:  
FB PAR 12  
ACSM1:  
FBA PAR12  
ACS850:  
FBA par12  
ACS880:  
TPDO1-EV time  
0 = Disable  
Event timer is disabled.  
Event time in ms.  
1…65535 (ms)  
RPDO6-COB-ID  
13  
Defines the COB-ID for Rx PDO6.  
0 =  
Disable  
Note: It is recommended to use the default  
COB-ID.  
ACS355:  
FB PAR 13  
ACSM1:  
FBA PAR13  
ACS850:  
FBA par13  
ACS880:  
RPDO6-COB-ID  
0 = Disable  
Rx PDO6 is not valid (disabled). COB-ID is  
80000300h + Node-ID.  
1 = Default  
Rx PDO6 is valid and configured to use the  
default COB-ID (300h + Node-ID).  
385…1407 (dec) = Rx PDO1 is valid and configured to use a  
181h … 57Fh  
custom COB-ID defined with this parameter.  
COB-ID must be within the allowed PDO COB-  
ID range (181h - 57Fh).  
Start-up 43  
No. Name/Value  
Description  
Default  
setting  
14  
RPDO6-TR TYPE Defines the Rx PDO6 transmission type. See  
255  
chapter Appendix A – Dictionary structure and  
entries.  
ACS355:  
FB PAR 14  
ACSM1:  
FBA PAR14  
ACS850:  
FBA par14  
ACS880:  
RPDO6-TR type  
0…255 (dec)  
Rx PDO6 transmission type. See section  
Description of transmission type on page 158.  
15  
RPDO6-EV TIME  
Defines the event time (time-out time) for the  
Rx PDO6 in the asynchronous transmission  
0 =  
Disable  
ACS355:  
FB PAR 15  
mode. If the Rx PDO6 communication between  
the adapter module and the bus master fails,  
the adapter module sets the communication  
between the module and the drive to the off-line  
mode.  
ACSM1:  
FBA PAR15  
ACS850:  
Event timer (time-out timer) elapses as a  
multiple of 1 ms of the entry of this parameter.  
Note: The time-out supervision is activated  
upon a successful reception of an Rx PDO6.  
FBA par15  
ACS880:  
RPDO6-EV time  
0 = Disable  
Time-out supervision is disabled.  
Event time in ms.  
1…65535 (ms)  
TPDO6-COB-ID  
16  
Defines the COB-ID for Tx PDO6.  
0 =  
Disable  
Note: It is recommended to use the default  
COB-ID.  
ACS355:  
FB PAR 16  
ACSM1:  
FBA PAR16  
ACS850:  
FBA par16  
ACS880:  
TPDO6-COB-ID  
0 = Disable  
Tx PDO6 is not valid (disabled). COB-ID is  
80000280h + Node-ID.  
1 = Default  
Tx PDO6 is valid and configured to use the  
default COB-ID (280h + Node-ID).  
385…1407 (dec) = Tx PDO6 is valid and configured to use a  
181h … 57Fh  
custom COB-ID defined with this parameter.  
COB-ID must be within the allowed PDO COB-  
ID range (181h - 57Fh).  
44 Start-up  
No. Name/Value  
Description  
Default  
setting  
17  
TPDO6-TR TYPE Defines the Tx PDO6 transmission type. See  
255  
chapter Appendix A – Dictionary structure and  
entries.  
ACS355:  
FB PAR 17  
ACSM1:  
FBA PAR17  
ACS850:  
FBA par17  
ACS880:  
TPDO6-TR type  
0…255 (dec)  
Tx PDO6 transmission type. See section  
Description of transmission type on page 158.  
18  
TPDO6-EV TIME  
Defines the event time for the Tx PDO6  
asynchronous transmission mode.  
0 =  
Disable  
ACS355:  
FB PAR 18  
Event timer elapses as a multiple of 1 ms of the  
entry of this parameter.  
ACSM1:  
FBA PAR18  
ACS850:  
FBA par18  
ACS880:  
TPDO6-EV time  
0 = Disable  
Event timer is disabled.  
Event time in ms.  
1…65535 (ms)  
RPDO21-COB-ID  
19  
Defines the COB-ID for Rx PDO21.  
0 =  
Disable  
Note: It is recommended to use the default  
COB-ID.  
ACS355:  
FB PAR 19  
ACSM1:  
FBA PAR19  
ACS850:  
FBA par19  
ACS880:  
RPDO21-COB-ID  
0 = Disable  
Rx PDO21 is not valid (disabled). COB-ID is  
80000400h + Node-ID.  
1 = Default  
Rx PDO21 is valid and configured to use the  
default COB-ID (400h + Node-ID).  
385…1407 (dec) = Rx PDO21 is valid and configured to use a  
181h … 57Fh  
custom COB-ID defined with this parameter.  
COB-ID must be within the allowed PDO COB-  
ID range (181h - 57Fh).  
Start-up 45  
No. Name/Value  
Description  
Default  
setting  
20  
RPDO21-TR  
TYPE  
Defines the Rx PDO21 transmission type. See 255  
chapter Appendix A – Dictionary structure and  
entries.  
ACS355:  
FB PAR 20  
ACSM1:  
FBA PAR20  
ACS850:  
FBA par20  
ACS880:  
RPDO21-TR type  
0…255 (dec)  
Rx PDO21 transmission type. See section  
Description of transmission type on page 158.  
21  
RPDO21-EV TIME Defines the event time (time-out time) for the  
Rx PDO21 in the asynchronous transmission  
0 =  
Disable  
ACS355:  
mode. If the Rx PDO21 communication  
between the adapter module and the bus  
master fails, the adapter module sets the  
communication between the module and the  
drive to the off-line mode.  
FB PAR 21  
ACSM1:  
FBA PAR21  
ACS850:  
Event timer (time-out timer) elapses as a  
multiple of 1 ms of the entry of this parameter.  
Note: The time-out supervision is activated  
upon a successful reception of an Rx PDO21.  
FBA par21  
ACS880:  
RPDO21-EV time  
0 = Disable  
Time-out supervision is disabled.  
Event time in ms.  
1…65535 (ms)  
46 Start-up  
No. Name/Value  
Description  
Default  
setting  
22  
TPDO21-COB-ID  
Defines the COB-ID for Tx PDO21.  
0 =  
Disable  
Note: It is recommended to use the default  
COB-ID.  
ACS355:  
FB PAR 22  
ACSM1:  
FBA PAR22  
ACS850:  
FBA par22  
ACS880:  
TPDO21-COB-ID  
0 = Disable  
Tx PDO21 is not valid (disabled). COB-ID is  
80000380h + Node-ID.  
1 = Default  
Tx PDO21 is valid and configured to use the  
default COB-ID (380h + Node-ID).  
385…1407 (dec) = Tx PDO21 is valid and configured to use a  
181h … 57Fh  
custom COB-ID defined with this parameter.  
COB-ID must be within the allowed PDO COB-  
ID range (181h - 57Fh).  
23  
TPDO21-TR  
TYPE  
Defines the Tx PDO21 transmission type. See  
chapter Appendix A – Dictionary structure and  
entries.  
255  
ACS355:  
FB PAR 23  
ACSM1:  
FBA PAR23  
ACS850:  
FBA par23  
ACS880:  
TPDO21-TR type  
0…255 (dec)  
Tx PDO21 transmission type. See section  
Description of transmission type on page 158.  
Start-up 47  
No. Name/Value  
Description  
Default  
setting  
24  
TPDO21-EV TIME Defines the event time for the Tx PDO21  
0 =  
asynchronous transmission mode.  
Disable  
ACS355:  
FB PAR 23  
Event timer elapses as a multiple of 1 ms of the  
entry of this parameter.  
ACSM1:  
FBA PAR23  
ACS850:  
FBA par23  
ACS880:  
TPDO21-EV time  
0 = Disable  
1...65535 (ms)  
Reserved  
Event timer is disabled.  
Event time in ms.  
25  
26  
Not used by the adapter module.  
N/A  
27  
FBA PAR  
REFRESH  
Validates any changed adapter module  
configuration parameter settings. After  
refreshing, the value reverts automatically to 0  
= Done.  
Note: This parameter cannot be changed while  
the drive is running.  
0 = Done  
ACS355/  
ACSM1:  
FBA PAR  
REFRESH  
ACS850/ACS880:  
FBA par refresh  
0 = Done  
Refreshing done  
Refreshing  
1 =  
Refresh/Configure  
28  
PAR TABLE VER  
Read-only. Displays the parameter table  
revision of the fieldbus adapter module  
mapping file stored in the memory of the drive.  
In format xyz, where:  
x = major revision number  
y = minor revision number  
x = correction number  
N/A  
ACS355:  
FILE CPI FW REV  
ACSM1:  
PAR TABLE VER  
ACS850/ACS880:  
Par table ver  
OR  
in format axyz, where  
a = major revision number  
xy = minor revision numbers  
z = correction number or letter.  
Parameter table revision  
48 Start-up  
No. Name/Value  
Description  
Default  
setting  
29  
DRIVE TYPE  
CODE  
Read-only. Displays the drive type code of the N/A  
fieldbus adapter module mapping file stored in  
the memory of the drive.  
ACS355:  
FILE CONFIG ID  
ACSM1:  
DRIVE TYPE  
COD  
ACS850/ACS880:  
Drive type code  
Drive type code of the fieldbus adapter module  
mapping file  
30  
MAPPING FILE  
VER  
Read-only. Displays the fieldbus adapter  
module mapping file revision stored in the  
memory of the drive in decimal format.  
N/A  
ACS355:  
FILE CONFIG  
REV  
ACSM1:  
MAPPING FILE  
VER  
ACS850/ACS880:  
Mapping file ver  
Mapping file revision  
Start-up 49  
No. Name/Value  
Description  
Default  
setting  
31  
D2FBA COMM  
STA  
Read-only. Displays the status of the fieldbus  
adapter module communication.  
0 = Idle  
OR  
Note: The value names may vary by drive.  
4 = Off-  
line  
ACS355:  
FBA STATUS  
ACSM1:  
D2FBA COMM  
STA  
ACS850/ACS880:  
D2FBA comm sta  
0 = Idle  
Adapter is not configured.  
Adapter is initializing.  
1 = Exec.init  
2 = Time out  
Time-out has occurred in the communication  
between the adapter and the drive.  
3 = Conf.err  
Adapter configuration error: Major or minor  
revision code of the common program revision  
in the fieldbus adapter module is not the  
revision required by the module or mapping file  
upload has failed more than three times.  
4 = Off-line  
5 = On-line  
6 = Reset  
Adapter is off-line.  
Adapter is on-line.  
Adapter is performing a hardware reset.  
32  
FBA COMM SW  
REV  
Read-only. Displays the common program  
revision of the adapter module in format axyz,  
where:  
N/A  
ACS355:  
FBA CPI FW REV  
a = major revision number  
xy = minor revision numbers  
z = correction number or letter.  
Example: 190A = revision 1.90A  
ACSM1:  
FBA COMM SW  
VER  
ACS850/ACS880:  
FBA comm SW  
rev  
Common program version of the adapter  
module  
50 Start-up  
No. Name/Value  
Description  
Default  
setting  
33  
FBA COMM APPL Read-only. Displays the application program  
N/A  
REV  
revision of the adapter module in format axyz,  
where:  
a = major revision number  
xy = minor revision numbers  
z = correction number or letter.  
Example: 190A = revision 1.90A  
ACS355:  
FBA CPI APPL  
REV  
ACSM1:  
FBA COMM APPL  
VER  
ACS850/ACS880:  
FBA appl SW ver  
Application program revision of the adapter  
module  
Start-up 51  
FCAN-01 configuration parameters – group B (group 2)  
Note: The actual parameter group number depends on the drive  
type. Group B (group 2) corresponds to:  
parameter group 55 in ACS355  
group 53 in ACSM1 and ACS850  
parameter group 53 in ACS880 if the adapter is installed as  
fieldbus adapter A or group 56 if the adapter is installed as  
fieldbus adapter B.  
1)  
2)  
No.  
01  
Name /Value  
Description  
Default  
For ACS355:  
Rx PDO1 word 2  
Selects data word 1 received by the drive over  
the CANopen network. From the drive's  
0 = Not  
used  
For other drives: perspective this corresponds to Rx PDO  
Rx PDO1 word 1  
communication in CANopen.  
ACS355:  
FBA DATA OUT 1  
CANopen  
master  
ABB drive  
ACSM1:  
FBA DATA OUT1  
ACS850/ACS880:  
FBA data out1  
Control word (CW)  
References  
FBA DATA OUT  
(Rx PDO)  
Content is defined by a decimal number in the  
range of 0 to 9999 as follows:  
0
Not used  
1…99 Virtual address area of drive control  
101… Parameter area of the drive  
9999  
See also Additional information on the virtual  
address area allocation on page 57.  
Note: The FCAN-01 configuration parameters  
are 16-bit parameters. If the mapped parameter  
is a 32-bit parameter, it automatically reserves  
two consecutive parameters. For example,  
mapping of a 32-bit parameter to parameter no.  
1 also reserves parameter no. 2.  
Note: In ACS355 drives, Rx PDO1 word 1 and  
Rx PDO6 word 1 are fixed and always mapped  
to object 6040h Control word. The first  
configuration parameters have effect on the 2nd  
words of these PDOs in ACS355 drives.  
 
52 Start-up  
1)  
2)  
No.  
Name /Value  
0 = None  
Description  
Default  
Not used  
1 = CW 16bit  
2 = Ref1 16bit  
3 = Ref2 16bit  
11 = CW 32bit  
12 = Ref1 32bit  
13 = Ref2 32bit  
101…9999  
Control word (16 bits)  
Reference REF1 (16 bits)  
Reference REF2 (16 bits)  
Control word (32 bits)  
Reference REF1 (32 bits)  
Reference REF2 (32 bits)  
Parameter number with format xxyy, where:  
xx is the parameter group number (1 to 99)  
yy is the parameter number index within that  
group (01 to 99).  
Note: In ACS880, choose Other to display a list  
of mappable drive parameters.  
02  
03  
04  
05  
06  
07  
08  
For ACS355:  
See parameter 01 above.  
See parameter 01 above.  
See parameter 01 above.  
See parameter 01 above.  
See parameter 01 above.  
See parameter 01 above.  
See parameter 01 above.  
0
0
0
0
0
0
0
Rx PDO1 word 3  
For other drives:  
Rx PDO1 word 2  
For ACS355:  
Rx PDO1 word 4  
For other drives:  
Rx PDO1 word 3  
For ACS355:  
Rx PDO6 word 2  
For other drives:  
Rx PDO1 word 4  
For ACS355:  
Rx PDO6 word 3  
For other drives:  
Rx PDO6 word 1  
For ACS355:  
Rx PDO6 word 4  
For other drives:  
Rx PDO6 word 2  
For ACS355:  
Rx PDO21 word 1  
For other drives:  
Rx PDO6 word 3  
For ACS355:  
Rx PDO21 word 2  
For other drives:  
Rx PDO6 word 4  
Start-up 53  
1)  
2)  
No.  
Name /Value  
Description  
Default  
09  
For ACS355:  
See parameter 01 above.  
0
Rx PDO21 word 3  
For other drives:  
Rx PDO21 word 1  
10  
11  
For ACS355:  
See parameter 01 above.  
0
0
0
Rx PDO21 word 4  
For other drives:  
Rx PDO21 word 2  
For ACS355:  
N/A  
For other drives:  
Rx PDO21 word 3  
See parameter 01 above.  
Note: ACS355 has only ten FBA DATA OUT  
parameters, indexes 1 to 10.  
12  
1)  
For ACS355:  
N/A  
For other drives:  
Rx PDO21 word 4  
See parameter 01 above.  
Note: ACS355 has only ten FBA DATA OUT  
parameters, indexes 1 to 10.  
The number of parameters in this group may vary by drive type and drive firmware.  
2)  
For more information, see chapter Communication protocol.  
54 Start-up  
FCAN-01 configuration parameters – group C (group 3)  
Note: The actual parameter group number depends on the drive  
type. Group C (group 3) corresponds to:  
parameter group 54 in ACS355  
group 52 in ACSM1 and ACS850  
parameter group 52 in ACS880 if the adapter is installed as  
fieldbus adapter A or group 55 if the adapter is installed as  
fieldbus adapter B.  
1)  
2)  
No.  
01  
Name /Value  
Description  
Default  
For ACS355:  
Data word 1 sent by the drive over the  
0 = Not  
Tx PDO1 word 2  
CANopen network. From the drive's perspective used  
For other drives: this corresponds to Tx PDO communication in  
Tx PDO1 word 1  
CANopen.  
ACS355:  
FBA DATA IN 1  
CANopen  
master  
ABB drive  
ACSM1:  
FBA DATA IN1  
ACS850/ACS880:  
FBA data in1  
FBA DATA IN  
(Tx PDO)  
Status word (SW)  
Actual values  
Content is defined by a decimal number in the  
range of 0 to 9999 as follows:  
0
Not used  
1…99 Virtual address area of drive control  
101… Parameter area of the drive  
9999  
See also Additional information on the virtual  
address area allocation on page 57.  
Note: The FCAN-01 configuration parameters  
are 16-bit parameters. If the mapped parameter  
is a 32-bit parameter, it automatically reserves  
two consecutive parameters. For example,  
mapping of a 32-bit parameter to parameter no.  
1 also reserves parameter no. 2.  
Note: In ACS355 drives, Tx PDO1 word 1 and  
Tx PDO6 word 1 are fixed and always mapped  
to object 6041h Status word. The first  
configuration parameters have effect on the 2nd  
words of these PDOs in ACS355 drives.